X3 Ultra Inverter Information
The X3 Ultra has two separate battery ports for two strings of batteries, here's some data on the inverter's battery port.
Table 1 Battery Port Data
Inverter Type |
X3-ULT-15K/19.9K/20K/25K/30K |
Battery voltage range [V ] |
180*-800 |
Max. charge / Discharge current [A ] |
30 × 2 |
*The voltage range of the battery port will be reduced shortly.
Compatibility
The X3 Ultra is available with the following 5 types of batteries. More types of batteries are being adapted, please stay tuned.
Figure 1 Batteries for X3 Ultra
Table 2 Battery Comparison
Battery Type |
Each Port |
Battery Heating |
Battery Extend |
Advantages |
Notes |
HS25/36 |
4~13 |
Yes |
TCBOX-70
(Supports 3 strings) |
1. Attractive Design
2. Easy installation, plug and play
3. Large capacity for system expansion.
4. Large charge and discharge current, which can accelerate the charging speed. |
1. The maximum quantity of one tower is 8pcs. If the number of HS batteries on one terminal ≥ 9pcs, a Series Box is required. 2. The battery heating function is under development. |
HS51 |
3~13 |
Yes |
TCBOX-70
(Supports 3 strings) |
1. Attractive Design
2. Easy installation, plug and play
3. Large capacity for system expansion.
4. Large charge and discharge current, which can accelerate the charging speed. |
1. The maximum quantity of one tower is 8pcs. If the number of HS batteries on one terminal ≥ 8pcs, a Series Box is required.
|
HR25/36 |
4~13 |
No |
TCBOX-70
(Supports 3 strings) |
1. Industrial Style Design
2. Easy installation
3. Large capacity for system expansion. |
|
T58 |
2~4 |
No |
BMS Parallel |
Large single |
|
|
|
|
Box G2
(Supports 2 strings) |
battery capacity |
|
|
Single and Dual Battery Port Solution
Battery Solution
1. HS(HR)25/36 and HS51 1 in 1 Solution
Figure 2 X3 Ultra+One BAT port
Figure 3 X3 Ultra+two BAT port
Table 3 Basic Data for 1 in 1 Solution
|
T-BAT-SYS-HV-S2.5 |
T-BAT-SYS-HV-S3.6 |
TSYS-HS51 |
Adaptable Quantity |
(4-13) × 2 pcs |
(4-13) × 2 pcs |
(3-13) × 2 pcs |
Total Capacity[kWh] |
(10.2-33.2) × 2 |
(14.7-47.9) × 2 |
(15.3-66.5)× 2 |
Max. charge / discharge current [A ] |
30 × 2 |
30 × 2 |
30 × 2 |
Nominal voltage [V ] |
204.8-665.6 |
204.8-665.6 |
153.6-665.6 |
Power [kW] |
(6.1-19.9) × 2 |
(6.1-19.9) × 2 |
(6.1-19.9) × 2 |
2. HS2.5/3.6 and HS51 2 in 1 Solution
The X3 ultra supports paralleling two battery ports together via a 2-in-1 paralleling cable, which allows the battery to pass a higher current, allowing the battery to be charged and discharged to its full matching power.
Figure 4 X3 Ultra + 2-in-1 cable+HS 2.5/3.6
Table 4 Basic Data for HS25/36 2 in 1 Solution
|
T-BAT-SYS-HV-S2.5 |
T-BAT-SYS-HV-S3.6 |
TSYS-HS51 |
Adaptable Quantity |
4-13 pcs |
4-13 pcs |
3-13 pcs |
Total Capacity[kWh] |
10-33.2 |
14.7-47.9 |
15.3-66.5 |
Max. charge / discharge current [A ] |
45A |
50A |
60A |
Nominal voltage [V ] |
204.8-665.6 |
204.8-665.6 |
153.6-665.6 |
Power [kW] |
9.2-29.9 |
10.2-33.2 |
10.8-44.6 |
2. T58 1 in 1 Solution
Figure 5 X3 Ultra + One BAT port
Figure 6 X3 Ultra + Two BAT port
Table 5 Basic Data for T58 Separate BAT Solution
|
T-BAT H 5.8 |
Adaptable Quantity |
(2-4) × 2 pcs |
Total Capacity[kWh] |
(11.5-23) × 2 |
Max. charge / discharge current [A ] |
30 × 2 |
Nominal voltage [V ] |
230.4-460.8 |
Power [kW] |
(6.9-13.8) × 2 |
3. T30 1 in 1 Solution
Figure 7 X3 Ultra + One BAT port
Figure 8 X3 Ultra + Two BAT port
Table 6 Basic Data for T30 Normal Solution
|
T-BAT H 3.0 |
Adaptable Quantity |
(2-4) × 2 pcs |
Total Capacity[kWh] |
(6.1-12.3kWh) × 2 |
Max. charge / discharge current [A ] |
30 × 2 |
Nominal voltage [V ] |
204.8 -409.6 |
Power [kW] |
(6.1-12.3) × 2 |
Battery Extend
X3 Ultra can realize battery extend by various accessories adaptable with different batteries, such as TCBOX-70 and BMS Parallel Box G2. And please note that the number of batteries in both strings needs to be the same.
1. HS(HR)2.5/3.6 and HS51 TC-Box-70 Solution
Figure 9 X3 Ultra + TC-Box-70+HS 2.5/3.6
Table 7 Basic Data for HS2.5/3.6/51 TC-Box-70 Solution
|
T-BAT-SYS-HV-S2.5 |
T-BAT-SYS-HV-S3.6 |
TSYS-HS51 |
Adaptable Quantity |
(4-13) × 6 pcs |
(4-13) × 6 pcs |
(3-13)x6 pcs |
Total Capacity[kWh] |
(10-32.5) × 6 |
(14.7-47.9) × 6 |
(15.3-66.5)x6 |
Max. charge / discharge current [A ] |
30 × 2 |
30 × 2 |
30x2 |
Nominal voltage [V ] |
204.8-665.6 |
204.8-665.6 |
204.8-665.6 |
Power [kW] |
(6.1-19.9) × 2 |
(6.1-19.9) × 2 |
(6.1-19.9) × 2 |
2. T58 BMS Parallel Box II G2 Solution
Figure 7 X3 Ultra + BMS Parallel Box II G2 +T58
Table 8 Basic Data for T58 BMS Parallel Box G2 Solution
|
T-BAT H 5.8 |
Adaptable Quantity |
(4 or 6 or 8) × 2 pcs |
Total Capacity[kWh] |
(23 or 34.6 or 46.1) × 2 |
Max. charge / discharge current [A ] |
30× 2 |
Nominal voltage [V ] |
230.4 or 345.6 or 460.8 |
Power [kW] |
(6.9 or 10.4 or 13.8)× 2 |
3. T30 BMS Parallel Box II G2 Solution
Figure 11 T30+BMS Parallel Box II G2
Table 9 Basic Data for T30 BMS Parallel Box II G2 Solution
|
T-BAT H 3.0 |
Adaptable Quantity |
(4 or 6 or 8) × 2 pcs |
Total Capacity[kWh] |
(12.3-24.6) × 2[kWh] |
Max. charge / discharge current [A ] |
30 × 2 |
Nominal voltage [V ] |
204.8 -409.6 |
Power [kW] |
(6.1-12.2) × 2 |
System and Battery extend
1. External Parallel(Up to 3pcs)
The X3-Ultra supports 3pcs internal switching parallel. Here is the data for each type of battery with their compatible parallel box.
Table 10 Data for external parallel solution
Battery Type |
HS(HR)25/36/51 |
T58 |
T30 |
Accessories |
TCBOX-70 |
BMS Parallel Box G2 |
BMS Parallel Box G2 |
Quantity |
6 ×13×3pcs |
4 ×4 ×3pcs |
4 ×4 ×3pcs |
Capacity[kWh] |
585/862.2/1197 |
276k |
147.6 |
2. External Parallel Solution(Up to 5pcs)
The X3-Ultra supports 5 pcs external switching parallel, and when extending the number of batteries in both strings needs to be the same.
① HS(HR)25/36/51
Figure 12 X3 Ultra + EPS Parallel Box G2.1-150K(adaptable with X3 Ultra)+ HS25/36 Table 11 Basic Data for External Switching Parallel Solution
|
T-BAT-SYS-HV-S2 .5 |
T-BAT-SYS-HV-S3.6 |
TSYS-HS51 |
Adaptable Quantity |
(4-13) × 6 × 5 pcs |
(4-13) × 6 × 5 pcs |
(3-13) × 6 × 5 pcs |
Total Capacity[kWh] |
(10-33.2) × 6 × 5 |
(14.7-47.9) × 6 × 5 |
(15.3-66.5.) × 6 × 5 |
Max. charge / discharge current [A ] |
30 × 2 |
30 × 2 |
30 × 2 |
Nominal voltage [V ] |
204.8-665.6 |
204.8-665.6 |
204.8-665.6 |
Power [kW] |
(6.1-19.9) × 6 × 5 |
(6.1-19.9) × 6 × 5 |
②T58
Figure 13 X3 Ultra + BMS Parallel Box G2 +
EPS Parallel Box G2.1-150K(adaptable with X3 Ultra)+T58 Table 12 Basic Data for External switching parallel Solution
|
T-BAT H 5.8 |
Adaptable Quantity |
(4 or 6 or 8) × 2 × 5 pcs |
Total Capacity[kWh] |
(23 or 34.6 or 46.1) × 2 × 5 |
Max. charge / discharge current [A ] |
30 × 2 |
Nominal voltage [V ] |
230.4 or 345.6 or 460.8 |
Power [kW] |
(6.9 or 10.4 or 13.8)× 2 × 5 |
③T30
Figure 14 X3 Ultra + BMS Parallel Box G2 +EPS Parallel Box G2.1-150K+T30 Table 13 Basic Data for External switching parallel Solution
|
T-BAT H 3.0 |
Adaptable Quantity |
(4 or 6 or 8) × 2 × 5 pcs |
Total Capacity[kWh] |
(12.3-24.6) × 2 × 5 |
Max. charge / discharge current [A ] |
30 × 2 |
Nominal voltage [V ] |
204.8 -409.6 |
Power [kW] |
(6.1-12.2) × 2 × 5 |
3. X3-Ultra external-switching 10 pcs parallel programme is being planned, please stay tuned!