X1/X3 Hybrid G4 Battery Selection
Here's some data on the inverter's battery port of X1 Hybrid G4.
Table 1 Battery Port Data
| Inverter Type | X1-Hybrid-G4 |
|---|---|
| Battery voltage range [V] | 80-480 |
| Max. charge / Discharge current [A] | 30 |
The X1-Hybrid G4 is available with the following types of batteries

1. T30 Normal Solution
Table 2 Basic Data for T30 Normal Solution
| Battery Type | T-BAT H 3.0 |
|---|---|
| Adaptable Quantity | 1-4 pcs |
| Total Capacity | 3.1-12.3 kWh |
| Max. charge / discharge current [A] | 30 |
| Nominal voltage [V] | 102.4-409.6 |
| Power [kW] | 3.0-12.2 |
2. T30 BMS Parallel Box II G2 Solution
• Each BMS Parallel Box G2 can connect 2 strings battery.
• The number of batteries in both strings needs to be the same
Table 3 Basic Data for T30 BMS Parallel Box II G2 Solution
| Battery Type | T-BAT H 3.0 |
|---|---|
| Adaptable Quantity | 2 or 4 or 6 or 8 pcs |
| Total Capacity | 6.1 or 12.3 or 18.4 or 24.4 kWh |
| Max. charge / discharge current [A] | 30× 2 |
| Nominal voltage [V] | 102.4-409.6 |
| Power [kW] | (3.0 or 6.1 or 9.2 or 12.2)× 2 |
3. Parallel Solution
• Each X1 Hybrid G4 can be paralleled by internal switch up to 2 pcs.
• Each BMS Parallel Box G2 can connect 2 strings battery, total of 4 strings.
• The number of batteries in both strings needs to be the same.
Table 4 Basic Data for Parallel Solution
| Battery Type | T-BAT H 3.0 |
|---|---|
| Adaptable Quantity | (2 or 4 or 6 or 8)× 2 pcs |
| Total Capacity | (6.1 or 12.3 or 18.4 or 24.4) × 2 kWh |
| Max. charge / discharge current [A] | 30× 2× 2 |
| Nominal voltage [V] | 102.4-409.6 |
| Power [kW] | (3.0 or 6.1 or 9.2 or 12.2)× 2× 2 |
1.T58 Normal Solution
Table 5 Basic Data for Parallel Solution
| Battery Type | T-BAT H 5.8 |
|---|---|
| Adaptable Quantity | 1-3 pcs |
| Total Capacity | 5.8-17.3 kWh |
| Max. charge / discharge current [A] | 30× 2× 2 |
| Nominal voltage [V] | 115.2-345.6 |
| Power [kW] | 3.4-10.3 |
1. T58 BMS Parallel Box II Solution
• The BMS Parallel Box II can connect 2 strings of batteries.
• If both strings of batteries are connected, the number of batteries in these both strings must be the same.
• In this solution, the X1 Hybrid G4 can be adaptable to 1-4 or 6 batteries.
Table 6 Basic Data for Parallel Solution
| Battery Type | T-BAT H 5.8 |
|---|---|
| Adaptable Quantity | 1-4 or 6 |
| Total Capacity | 5.8-23.0 or 34.6 kWh |
| Max. charge / discharge current [A] | 30× 2 |
| Nominal voltage [V] | 115.2-460.8 or 345.6 |
| Power [kW] | 3.4-13.8 or 10.3 |
2. T58 BMS Parallel Box II G2 Solution
①BMS Parallel Box II can only match with T58, while G2 can match with T30 in addition to T58;
②BMS Parallel Box II two towers of batteries have the same bottom terminals, while G2 two towers of batteries have different bottom terminals, divided into Main port and Slave port;
③Taking T58 batteries as an example, both BMS Parallel Box II towers can only be connected to T58 slave (i.e. HV11550), while G2 Main tower needs to be connected to BMS, and Slave tower only needs to be connected to slave control;
• The BMS Parallel Box II G2 can connect 2 strings of batteries.
• If both strings of batteries are connected, the number of batteries in these both strings must be the same.
• In this solution, the X1 Hybrid G4 can be adaptable to 2 or 4 or 6 batteries.
• Each X1 Hybrid G4 can be paralleled by internal switch up to 2 pcs, and the X1 Hybrid G4 can be adaptable to (2 or 4 or 6) × 2 batteries in this condition.
Table 7 Basic Data for T58 BMS Parallel Box II G2 Solution
| Battery Type | T-BAT H 5.8 |
|---|---|
| Adaptable Quantity | 2 or 4 or 6 |
| Total Capacity | 11.5 or 23.0 or 34.6 kWh |
| Max. charge / discharge current [A] | 30× 2 |
| Nominal voltage [V] | 115.2 or 230.4 or 345.6 |
| Power [kW] | 3.4 or 6.9 or 10.3 |
1. HS25/36 Normal Solution
Table 8 Basic Data for HS25/36 Normal Solution
| Battery Type | HS25 | HS36 |
|---|---|---|
| Adaptable Quantity | 2-8 pcs | 2-8 pcs |
| Total Capacity | 5.1-20.4 kWh | 7.3-29.4 kWh |
| Max. charge / discharge current [A] | 30 | 30 |
| Nominal voltage [V] | 102.4-409.6 | 102.4-409.6 |
| Power [kW] | 3.0-12.2 | 3.0-12.2 |
1. HS 51 / 51O Normal Solution
Table 9 Basic Data for HS51/51O Normal Solution
| Battery Type | HS51 | HS51O |
|---|---|---|
| Adaptable Quantity | 2-8 pcs | 2-8 pcs |
| Total Capacity | 10.2-40.9 kWh | 10.2-40.9 kWh |
| Max. charge / discharge current [A] | 70 | 70 |
| Nominal voltage [V] | 102.4-409.6 | 102.4-409.6 |
| Power [kW] | 6.1-24.6 | 6.1-24.6 |
Here's some data on the inverter's battery port of X3 Hybrid G4.
Table 10 X3 G4 BAT Port Information
| Inverter Type | X3-Hybrid G4 |
|---|---|
| Battery voltage range [V] | 180-800 |
| Max. charge / Discharge current [A] | 30 |
The X3-Hybrid G4 is available with the following three types of batteries

X 3 Hybrid G4 Battery Selection——T30
1. T30 Normal Solution
Table 11 T30 Normal Solution
| Battery Type | T-BAT H 3.0 |
|---|---|
| Adaptable Quantity | 2-4 pcs |
| Total Capacity | 6.1-12.3 kWh |
| Max. charge / discharge current [A] | 30 |
| Nominal voltage [V] | 102.4-409.6 |
| Power [kW] | 6.0-12.2 |
2. T30 BMS Parallel Box II G2 Solution
• Each BMS Parallel Box G2 can connect 2 strings battery, total of 4 strings.
• The number of batteries in both strings needs to be the same
Table 12 T30 Normal Solution
| Battery Type | T-BAT H 3.0 |
|---|---|
| Adaptable Quantity | 4 or 6 or 8 pcs |
| Total Capacity | 12.3 or 18.4 or 24.6 kWh |
| Max. charge / discharge current [A] | 30× 2 |
| Nominal voltage [V] | 204.8 or 307.2 or 409.6 |
| Power [kW] | (6.0 or 9.2 or 12.2)× 2 |
3. External switching parallel Solution
• Each X3 Hybrid G4 can be paralleled by EPS Parallel Box up to 10 pcs.
• If the number of parallel inverters exceeds 3, the EPS parallel box must be used.
Table 13 External switching parallel Solution
| Battery Type | T-BAT H 3.0 |
|---|---|
| Adaptable Quantity | (4 or 6 or 8)× 10 pcs |
| Total Capacity | (12.3 or 18.4 or 24.6)× 10 kWh |
| Max. charge / discharge current [A] | 30× 2× 10 |
| Nominal voltage [V] | 204.8 or 307.2 or 409.6 |
| Power [kW] | (6.0 or 9.2 or 12.2)× 2× 10 |
1. T58 Normal Solution
Table 14 Data for T58 Normal Solution
| Battery Type | T-BAT H 5.8 |
|---|---|
| Adaptable Quantity | 2-4 pcs |
| Total Capacity | 11.5-23.0 kWh |
| Max. charge / discharge current [A] | 30 |
| Nominal voltage [V] | 230.4-460.8 |
| Power [kW] | 6.9-13.8 |
2. T58 BMS Parallel Box II Solution
• The BMS Parallel Box II can connect 2 strings of batteries.
• If both strings of batteries are connected, the number of batteries in these both strings must be the same.
• In this solution, the X1 Hybrid G4 can be adaptable to 2-4 or 6 batteries.
Table 15 Data for T58 BMS Parallel Box II Solution
| Battery Type | T-BAT H 5.8 |
|---|---|
| Adaptable Quantity | 2-4 or 6 pcs |
| Total Capacity | 115.2-230.4 or 345.6 or 460.8 kWh |
| Max. charge / discharge current [A] | 30× 2 |
| Nominal voltage [V] | 115.2-230.4 or 345.6 or 460.8 |
| Power [kW] | 3.4-13.8 |
3. T58 BMS Parallel Box II G2 Solution
• The BMS Parallel Box II G2 can connect 2 strings of batteries.
• If both strings of batteries are connected, the number of batteries in these both strings must be the same.
• In this solution, the X3 Hybrid G4 can be adaptable to 4 or 6 or 8 batteries.
Table 16 Data for T58 BMS Parallel Box II G2 Solution
| Battery Type | T-BAT H 5.8 |
|---|---|
| Adaptable Quantity | 4 or 6 or 8 pcs |
| Total Capacity | 23 or 34.6 or 46.1 kWh |
| Max. charge / discharge current [A] | 30× 2 |
| Nominal voltage [V] | 230.4-460.8 |
| Power [kW] | 6.9-13.8 |
4. External switching parallel Solution
1. HS25/36 Normal Solution
Table 17 Basic Data for HS25/36 Normal Solution
| Battery Type | HS25 | HS36 |
|---|---|---|
| Adaptable Quantity | 3-13 pcs | 3-13 pcs |
| Total Capacity | 7.6-33.2 kWh | 11.0-47.9 kWh |
| Max. charge / discharge current [A] | 30 | 30 |
| Nominal voltage [V] | 153.6-665.6 | 153.6-665.6 |
| Power [kW] | 4.6-19.9 | 5.3-23.2 |
2. External switching parallel Solution
• X3 Hybrid G4 can be paralleled by EPS Parallel Box up to 10 pcs.
• If the number of parallel inverters exceeds 3, the EPS parallel box must be used.
1. HS51/51O Normal Solution
Table 18 Basic Data for HS51/51O Normal Solution
| Battery Type | HS51 | HS51O |
|---|---|---|
| Adaptable Quantity | 3-13 pcs | 3-13 pcs |
| Total Capacity | 15.3-59.8 kWh | 15.3-59.8 kWh |
| Max. charge / discharge current [A] | 70 | 70 |
| Nominal voltage [V] | 153.6-665.6 | 153.6-665.6 |
| Power [kW] | 9.2-39.9 | 9.2-39.9 |
2. External switching parallel Solution
• X3 Hybrid G4 can be paralleled by EPS Parallel Box up to 10 pcs.
• If the number of parallel inverters exceeds 3, the EPS parallel box must be used.