Here's some data on the inverter's battery port of X1 Hybrid G4.
Table 1 Battery Port Data
|
Inverter Type |
X1-Hybrid-G4 |
|
Battery voltage range [V] |
80-480 |
|
Max. charge / Discharge current [A] |
30 |
The X1-Hybrid G4 is available with the following three types of batteries

Figure 1 Batteries for X1 Hybrid G4
1. T30 Normal Solution

Figure 2 X1 Hybrid G4+One BAT port
Note:
Table 2 Basic Data for T30 Normal Solution
|
Inverter Type |
T-BAT H 3.0 |
|
Adaptable Quantity |
1-4 pcs |
|
Total Capacity |
3.1-12.3 kWh |
|
Max. charge / discharge current [A] |
30 |
|
Nominal voltage [V] |
102.4-409.6 |
|
Power [kW] |
3.0-12.2 |
2. T30 BMS Parallel Box II G2 Solution

Figure 3 X1 Hybrid G4 + BMS Parallel Box II G2 + T30
Note:
Table 3 Basic Data for T30 BMS Parallel Box II G2 Solution
|
Inverter Type |
T-BAT H 3.0 |
|
Adaptable Quantity |
2 or 4 or 6 or 8 pcs |
|
Total Capacity |
6.1 or 12.3 or 18.4 or 24.4 kWh |
|
Max. charge / discharge current [A] |
30× 2 |
|
Nominal voltage [V] |
102.4-409.6 |
|
Power [kW] |
(3.0 or 6.1 or 9.2 or 12.2)× 2 |
3. Parallel Solution

Figure 4 X1 Hybrid G4 + BMS Parallel Box II G2 + T30
Note:
Table 4 Basic Data for Parallel Solution
|
Inverter Type |
T-BAT H 3.0 |
|
Adaptable Quantity |
(2 or 4 or 6 or 8)× 2 pcs |
|
Total Capacity |
(6.1 or 12.3 or 18.4 or 24.4) × 2 kWh |
|
Max. charge / discharge current [A] |
30× 2× 2 |
|
Nominal voltage [V] |
102.4-409.6 |
|
Power [kW] |
(3.0 or 6.1 or 9.2 or 12.2)× 2× 2 |
1.T58 Normal Solution

Figure 5 T58 Normal Solution
Note:
Table 5 Basic Data for Parallel Solution
|
Inverter Type |
T-BAT H 5.8 |
|
Adaptable Quantity |
1-3 pcs |
|
Total Capacity |
5.8-17.3 kWh |
|
Max. charge / discharge current [A] |
30× 2× 2 |
|
Nominal voltage [V] |
115.2-345.6 |
|
Power [kW] |
3.4-10.3 |
2. T58 BMS Parallel Box II Solution

Figure 6 X1 Hybrid G4 + BMS Parallel Box II + T58
Note:
Table 6 Basic Data for Parallel Solution
|
Inverter Type |
T-BAT H 5.8 |
|
Adaptable Quantity |
1-4 or 6 |
|
Total Capacity |
5.8-23.0 or 34.6 kWh |
|
Max. charge / discharge current [A] |
30× 2 |
|
Nominal voltage [V] |
115.2-460.8 or 345.6 |
|
Power [kW] |
3.4-13.8 or 10.3 |
3. T58 BMS Parallel Box II G2 Solution
①BMS Parallel Box II can only match with T58, while G2 can match with T30 in addition to T58;
②BMS Parallel Box II two towers of batteries have the same bottom terminals, while G2 two towers of batteries have different bottom terminals, divided into Main port and Slave port;
③Taking T58 batteries as an example, both BMS Parallel Box II towers can only be connected to T58 slave (i.e. HV11550), while G2 Main tower needs to be connected to BMS, and Slave tower only needs to be connected to slave control;

Figure 7 X1 Hybrid G4 + BMS Parallel Box II G2+ T58
Note:
Table 7 Basic Data for T58 BMS Parallel Box II G2 Solution
|
Inverter Type |
T-BAT H 5.8 |
|
Adaptable Quantity |
2 or 4 or 6 |
|
Total Capacity |
11.5 or 23.0 or 34.6 kWh |
|
Max. charge / discharge current [A] |
30× 2 |
|
Nominal voltage [V] |
115.2 or 230.4 or 345.6 |
|
Power [kW] |
3.4 or 6.9 or 10.3 |
1. HS25/36 Normal Solution

Figure 8 X1 Hybrid G4 + HS25/36
Note:
Table 8 Basic Data for HS25/36 Normal Solution
|
Inverter Type |
HS25 |
HS36 |
|
Adaptable Quantity |
2-8 pcs |
2-8 pcs |
|
Total Capacity |
5.1-20.4 kWh |
7.3-29.4 kWh |
|
Max. charge / discharge current [A] |
30 |
30 |
|
Nominal voltage [V] |
102.4-409.6 |
102.4-409.6 |
|
Power [kW] |
3.0-12.2 |
3.0-12.2 |
Here's some data on the inverter's battery port of X3 Hybrid G4.
Table 9 X3 G4 BAT Port Information
|
Inverter Type |
X3-Hybrid G4 |
|
Battery voltage range [V] |
180-800 |
|
Max. charge / Discharge current [A] |
30 |
The X3-Hybrid G4 is available with the following three types of batteries

Figure 9 Batteries for X3 Hybrid G4
1. T30 Normal Solution

Figure 10 X3 Hybrid G4 + T30
Note:
Table 10 T30 Normal Solution
|
Inverter Type |
T-BAT H 3.0 |
|
Adaptable Quantity |
2-4 pcs |
|
Total Capacity |
6.1-12.3 kWh |
|
Max. charge / discharge current [A] |
30 |
|
Nominal voltage [V] |
102.4-409.6 |
|
Power [kW] |
6.0-12.2 |
2. T30 BMS Parallel Box II G2 Solution

Figure 11 X3 Hybrid G4 + BMS Parallel Box II G2 + T30
Note:
Table 11 T30 Normal Solution
|
Inverter Type |
T-BAT H 3.0 |
|
Adaptable Quantity |
4 or 6 or 8 pcs |
|
Total Capacity |
12.3 or 18.4 or 24.6 kWh |
|
Max. charge / discharge current [A] |
30× 2 |
|
Nominal voltage [V] |
204.8 or 307.2 or 409.6 |
|
Power [kW] |
(6.0 or 9.2 or 12.2)× 2 |
3. External switching parallel Solution

Figure 12 X1 Hybrid G4 + EPS Parallel Box +BMS Parallel Box G2 + T30
Note:
Table 12 External switching parallel Solution
|
Inverter Type |
T-BAT H 3.0 |
|
Adaptable Quantity |
(4 or 6 or 8)× 10 pcs |
|
Total Capacity |
(12.3 or 18.4 or 24.6)× 10 kWh |
|
Max. charge / discharge current [A] |
30× 2× 10 |
|
Nominal voltage [V] |
204.8 or 307.2 or 409.6 |
|
Power [kW] |
(6.0 or 9.2 or 12.2)× 2× 10 |
1. T58 Normal Solution

Figure 13 T58 Normal Solution
Note:
Table 13 Data for T58 Normal Solution
|
Inverter Type |
T-BAT H 5.8 |
|
Adaptable Quantity |
2-4 pcs |
|
Total Capacity |
11.5-23.0 kWh |
|
Max. charge / discharge current [A] |
30 |
|
Nominal voltage [V] |
230.4-460.8 |
|
Power [kW] |
6.9-13.8 |
2. T58 BMS Parallel Box II Solution

Figure 14 X3 Hybrid G4 + BMS Parallel Box II + T58
Note:
Table 14 Data for T58 BMS Parallel Box II Solution
|
Inverter Type |
T-BAT H 5.8 |
|
Adaptable Quantity |
2-4 or 6 pcs |
|
Total Capacity |
115.2-230.4 or 345.6 or 460.8 kWh |
|
Max. charge / discharge current [A] |
30× 2 |
|
Nominal voltage [V] |
115.2-230.4 or 345.6 or 460.8 |
|
Power [kW] |
3.4-13.8 |
3. T58 BMS Parallel Box II G2 Solution

Figure 15 X3 Hybrid G4 + BMS Parallel Box II G2+ T58
Note:
Table 15 Data for T58 BMS Parallel Box II G2 Solution
|
Inverter Type |
T-BAT H 5.8 |
|
Adaptable Quantity |
4 or 6 or 8 pcs |
|
Total Capacity |
23 or 34.6 or 46.1 kWh |
|
Max. charge / discharge current [A] |
30× 2 |
|
Nominal voltage [V] |
230.4-460.8 |
|
Power [kW] |
6.9-13.8 |
4. External switching parallel Solution

Figure 16 X3 Hybrid G4 + EPS Parallel Box + BMS Parallel Box II G2 + T58
Note:
If the number of parallel inverters exceeds 3, the EPS parallel box must be used.
1. HS25/36 Normal Solution

Figure 17 X3 Hybrid G4 + HS25/36
Note:
Table 16 Basic Data for HS25/36 Normal Solution
|
Inverter Type |
HS25 |
HS36 |
|
Adaptable Quantity |
3-13 pcs |
3-13 pcs |
|
Total Capacity |
7.6-33.2 kWh |
11.0-47.9 kWh |
|
Max. charge / discharge current [A] |
30 |
30 |
|
Nominal voltage [V] |
153.6-665.6 |
153.6-665.6 |
|
Power [kW] |
4.6-19.9 |
5.3-23.2 |
2. External switching parallel Solution

Figure 18 X3 Hybrid G4 + EPS Parallel Box + HS25/36
Note: