| Revision History | About | Connection Diagram | Connection |
| Settings | Compatibility | Notes |
| Update time | Update details | Version | Writer |
|---|---|---|---|
| 2024.11.11 | Update details | V1.1 | Amara |
| 2026.5.27 | Add SolaX meter | V1.3 | Evan-蒋振豪 |
Generally, a single-phase inverter can realize zero injection to the grid only with a single-phase meter. However, in some cases, users want to install a single-phase inverter in a three-phase system. With a single-phase meter, the inverter can only realize one phase's export control, which is not suitable for a three-phase system.
SolaX single-phase inverters support connecting a SolaX three-phase meter or Chint three-phase meter to realize three phases export control (Total Mode). Total zero export control can work in such a case.
There are no special requirements for this connection. Just follow the installation instructions for each part, and the meter should be a SolaX or Chint three-phase meter.
The AC output of the inverter could be connected to any phase. A three-phase meter should be installed before the grid to give export control to the whole three-phase system. The connection of the three-phase meter is the same as in a normal three-phase system. Connect the signal cable to the Meter/CT port of the inverter.
For practical on-site system installation and implementation of export limitation (zero-export control), it is generally recommended to connect the single-phase inverter between the L3 phase and neutral (N) of the three-phase utility grid, as illustrated in the diagram above.
For single-phase loads, the load may be connected to any phase (L1, L2, or L3). For three-phase loads, the loads can be connected to the three-phase grid as shown in the diagram above.
Set export control to 0 if it is required.
|
Step 1
![]() |
Step 2
![]() |
Step 3
![]() |
If multiple single-phase string inverters are combined into a parallel system, such as the X1-Boost-G4, X1-Mini-G4, or X1-Smart-G2, and these inverters are connected to the same phase line, this KB solution can also be applied.
In this case, the export control setting changes to:
For details, please refer to the corresponding inverter user manual.
Please note that three or more single-phase string inverters can be used to form a three-phase grid. For detailed configuration requirements, please refer to the corresponding inverter user manual.
| Inverter | 3P SolaX Meter | 3P Chint Meter |
|---|---|---|
| X1-Mini-G4 | M3-40 | DTSU666 / DTSU666-CT |
| X1-Boost-G4 | M3-40 | DTSU666 / DTSU666-CT |
| X1-Smart-G2 | M3-40 | DTSU666 / DTSU666-CT |
| X1-IES | M3-40 | DTSU666 / DTSU666-CT |
| X1-Fit-G4 | M3-40 / M3-40 dual | DTSU666 / DTSU666-CT |
| X1-Hybrid-G4 | M3-40 / M3-40 dual | DTSU666 / DTSU666-CT |
| X1-Vast | M3-40 / M3-40 dual | DTSU666 / DTSU666-CT |