1. Earthing System
2. North American Grid System
3. EU Grid System
4. Latin American Grid System
5. Grid System in Japan
According to standard IEC 60364-3, the different grid earthing systems are defined as: TN, TT & IT systems; and the TN system is further separated into TN-C, TN-S, TN-C-S.
Thus you can understand the TN, TT & IT systems in the following notes:
Fig. 1
Next, we will give brief introduction of the grid systems in different global regions.
According to ANSI C84-la-1980, there are two different LV distribution grid types:
1 Split Phase - 120/240V
2 Delta - 208V&240V and Wye - 277/480V, 120/208V
The most common residential service in North America is split phase 120/240V, which are used to power 120V lighting and plug loads and power 240V single phase loads such as a water heater, electric range, or air conditioner.
For commercial building the most common electric service is 120/208V Wye, which is used to power 120V plug loads, lighting, and smaller HVAC systems. In larger facilities the voltage is 277/480V and used to power single phase 277 volt lighting and larger HVAC loads.
The following grid type is also known as a high-leg or wild-leg delta system. Usually used in older manufacturing facilities with mostly three-phase motor loads and some 120 volt single-phase lighting and plug loads.
In Europe, IT, TT, TN-C, TN-S, TN-C-S systems are commonly seen. The diagrams below will show the different LV distribution systems in Europe.
The commonly supplied power is 3-Phase Wye 220/380V same as Fig. 6. However there are some other special types of grid supply which are also different in Latin America.
For example, in some regions of Brazil, there is no standard voltage. The nominal voltage of 3-Phase Wye can be 127/220V, 125/216V, 220/380V and 230/400V as below:
Besides that, most federative units use 220 V electricity (three-phase) as below:
Similarly to North American Split Phase grid, Japan has the 100/200V split phase system for normal household power supply.