Sign in
Already have SolaX Cloud Installer Account
Or
Access to E-Learning
Contact Us
Contact Us
Our online learning platform is currently only open to Installer accounts in SolaX Cloud. If you wish to use the online platform,please send your account application to training.global@solaxpower.com
Home / Support / Solution / Details
Project design

    SolaX_VPP function Definition of ESS

    Instructions

    This document provides a comprehensive overview of the VPP functions of Solax energy storage inverters. Please note that not each type of energy storage inverters contains each of the following VPP control modes, please contact service support to find out which VPP control modes are included in a specific type of energy storage inverters.

    Remote control of Hybrid INV based on Modbus

    Remote Control Logical Introduction (required registers)

    Write multiple register

    Register

    Variable

    W/R

    Description

    Unit

    Data
    format

    Lenth

    0x007C

    ModbusPowerControl

    W

    0: disable remote control

    1: enable power control mode

    2: enable electric quantity target control mode (This is based on kWh as the command target)

    3: enable SOC target control mode (This is based on SOC as the command target)

    4: Push Power-Positive/Negative Mode

    5: Push Power – Zero Mode

    6: Self-Consume -Charge/Discharge Mode

    7: Self-Consume-Charge Only Mode

    1

    Uint16

    1

    0x007D

    TargetSetType

    W

    The response logic for receiving this target value: (for all modes)
    1: set: reset the target (After the target value is received for the second time, the current value is directly accumulated again)

    2: update: update the target (After receiving the target value for the second time, the data is accumulated to the second target value cut-off)

    1

    Uint16

    1

    0x007E
    ~0x007F

    RemoteControl ActivePower

    W

    0x007E(LSB)
    0x007F(MSB)

    (Positive means charge; Negative means discharge)

    (for mode 1:active power control)

    1W

    int32

    2

    0x0080
    ~0x0081

    RemoteControl ReactivePower

    W

    0x0080(LSB)
    0x0081(MSB)

    (Positive means Inductive reactive power; Negative means Capacitive reactive power)

    (for mode 1: Reactive Power control)

    1Var

    int32

    2

    0x0082

    Time_of_Duration

    W

    The duration time of the power control mode
    (for mode 1: How long should the current target value be maintained)

    1s

    Uint16

    1

    0x0083

    TargetSoc

    W

    SOC as target value

    (for mode 3)

    1%

    Uint16

    1

    0x0084
    ~0x0085

    TargetEnergy

    W

    0x0084(LSB)
    0x0085(MSB)

    electric quantity as target value

    (for mode 2)

    1Wh

    Uint32

    2

    0x0086
    ~0x0087

    Charge_Discharg_Power

    W

    0x0086(LSB)
    0x0087(MSB)

    The power of charging or discharging

    (Positive means charge; Negative means discharge)
    (for mode 2 and 3: how much power should be used to achieve the set target value)

    1W

    Int32

    2

    0x0088

    RemoteCtrlTimeOut

    W

    Timeout counter (for all modes)
    How long the current mode lasts after the set target value is completed, if not updated.

    Take the target completion as the mark bit, start timing, if it is not completed, no timing. For example, if RemoteCtrlTimeQut is set to 600s, then at 600 seconds after the target completion of the command, the device will exit Modbus Remote Control Mode and return to the mode it was in before entering Modbus Remote Control Mode.

    1s

    Uint16

    1

    0x0089

    ~0x008A

    PushModePower

    0x0089(LSB)
    0x008A(MSB)
    The power of battery charging or discharging
    (Positive means battery discharge; Negative means battery charge)

    (for mode 4)

    1W

    int32

    2

    0x00A0

    PowerControlMode

    W

    Select Power Control Mode

    8: PV&BAT Individual Setting – Duration Mode

    9: PV&BAT Individual Setting – Target SOC Mode

    1

    Uint16

    1

    0x00A1

    TargetSetType

    W

    1: Set Target

    2: Update Target

    1

    Uint16

    1

    0x00A2

    0x00A3

    PVPowerLimit

    W

    0x00A2: LSB of PV Power Limit

    0x00A3: MSB of PV Power Limit

    1W

    Uint32

    2

    0x00A4

    0x00A5

    PushModePower

    W

    Battery power target (positive discharge, negative charge)
    0x00A4: LSB of PushModePower

    0x00A5: MSB of PushModePower

    1W

    Int32

    2

    0xA6

    Time of Duration

    W

    Time of Duration: when choose mode 8

    (PowerControlMode == 8);

    1s

    Uint16

    1

    Target SOC

    Target SOC: when choose mode 9

    (PowerControlMode == 9);

    Range 0~100%

    1%

    Uint16

    1

    0xA7

    RemoteControlTimeOut

    W

    Remote Control Timeout

    1s

    Uint16

    1

    Operation Introduction

    Unlock the Controlled Device

    For parameter writing operation, unlocking process is required first. This unlock password is the same as the unlock password required before doing parameter setting locally on the inverter, and the default is "2014". After unlocking, the system will always be in the unlocked state unless an invalid password is written again or the system is rebooted.

    Unlock Address:

    Function code 0x06, register 0x0000

    You can also query the lock status of the device.

    Query Address:

    Function code 0x04, register 0x0054

    Parameter Setting of Remote Control (VPP)

    0x007C~0x008A is the index of Remote Control (VPP function) multi-write control (function code 0x10). When using it, please select the corresponding parameter to fill and write according to the required mode. For mode 1-7, depending on the current device mechanism, it is necessary to fill values for all registers in this mode. For mode 1-3, the registers that need to be filled with values are 0x007C~0x0088. For mode 4-7, the registers that need to be filled with values are 0x007C~0x008A. Filling any values in the registers that are not related to the current mode will not affect the current mode, and "0" is the necessary value for irrelevant registers. The feature to fill only the required registers is not supported yet, but it will be available soon. Please stay tuned.

    • Note: For inverters, the written values are recommended to be in hexadecimal data format and the two's complement format must be used, with particular attention to the format when setting negative values.

    Further details on how to set each parameter to realize various types of control can be found in Section 2.3 "Details of each mode" below, where for mode 1-7 only the registers needed for each mode are listed, the rest of the irrelevant registers need to be filled in as “0” as well.

    Details of each mode

    Mode 1: Power Control Mode

    Model 1 Description:

    This mode controls the active and reactive power at the AC port of the inverter for a period of time. In this mode the PV runs at the highest possible power and the system can feed/take power to/from the grid.

    Exit logic: The exit of mode 1 based on the two limit values, “Time_of_Duration” and “RemoteCtrlTimeOut”. That is, the “Time_of_Duration” is judged first, if during this period there is no new power target command, then continue to wait for the time of “RemoteCtrlTimeOut”, if “RemoteCtrlTimeOut” is satisfied, then the mode 1 is exited to the regular work mode of the inverter.

    The key of the model is that the system will try to meet the target power as much as possible.

    In this mode the AC port power target is positive for charging and negative for discharging; the battery input represents charging and the output represents discharging; the PV is always the input to the inverter.

    Control Mode

    Register

    Variable

    Unit

    mode 1

    (power control mode)

    0x007C

    ModbusPowerControl

    1

    0x007D

    TargetSetType

    1

    0x007E

    RemoteControl ActivePower

    1W

    0x007F

    0x0080

    RemoteControl ReactivePower

    1W

    0x0081

    0x0082

    Time_of_Duration

    1s

    0x0088

    RemoteCtrlTimeOut

    1s

     

    Case study 1.1:

    • Pre-commission:

    Inverter work mode: Self-Use Mode

    P(PV) = 2000W

    P(BAT) = 1000W (battery charging)

    P(AC) = -1000W (inverter output)

    P(Load) = 1000W (load consumption)

    Grid Meter = 0

    • User Requirement:

    Inverter AC port output active power 5000W;

    PV runs at maximum power if possible;

    The above state lasts for 5 minutes;

    • Write Command:

    Register

    Variable

    Unit

    Case Study 1.1

    (decimal)

    Write Value

    (hexadecimal)

    0x007C

    ModbusPowerControl

    1

    1

    0x0001

    0x007D

    TargetSetType

    1

    1

    0x0001

    0x007E

    RemoteControl ActivePower

    1W

    -5000

    0xEC78

    0x007F

    0xFFFF

    0x0080

    RemoteControl ReactivePower

    1W

    0

    0x0000

    0x0081

    0x0000

    0x0082

    Time_of_Duration

    1s

    300

    0x012C

    0x0088

    RemoteCtrlTimeOut

    1s

    600

    0x0258

    • Situation under Remote Control Mode 1 (for example only, not a real situation):

    Power Control Mode

    P(PV) = P(PV max) = 2000W (This is the maximum value in the example environment.)

    P(BAT) = -3000W (battery discharging)

    P(AC) = -5000W (inverter output)

    P(Load) = 1000W (load consumption)

    Grid Meter = 4000W (feed into grid)

    The above condition lasts for 300s and then the AC port stops outputting. After this continues for 600s, the inverter returns to Self-Use mode.

    Case study 1.2:

    • Pre-commission:

    Remote Control Mode 1 (VPP control); before entering this remote control mode 1, the inverter’s work mode is Backup mode.

    P(PV) = 4000W

    P(BAT) = 1000W (battery charging)

    P(AC) = -3000W (inverter output)

    P(Load) = 3000W (load consumption)

    Grid Meter = 0

    • User Requirement:

    Remote Control Mode 1 + Updated target

    Inverter AC port input active power 1000W;

    PV runs at maximum power if possible;

    The above state lasts for 5 minutes;

    • Write Command:

    Register

    Variable

    Unit

    Case Study 1.2

    (decimal)

    Write Value

    (hexadecimal)

    0x007C

    ModbusPowerControl

    1

    1

    0x0001

    0x007D

    TargetSetType

    1

    2

    0x0002

    0x007E

    RemoteControl ActivePower

    1W

    1000

    0x03E8

    0x007F

    0x0000

    0x0080

    RemoteControl ReactivePower

    1W

    0

    0x0000

    0x0081

    0x0000

    0x0082

    Time_of_Duration

    1s

    300

    0x012C

    0x0088

    RemoteCtrlTimeOut

    1s

    600

    0x0258

    • Situation under Remote Control Mode 1 (for example only, not a real situation):

    Power Control Mode

    P(PV) = P(PV max) = 4000W

    P(BAT) = P(BAT max) = 4500W (battery charging) (It is the maximum charging power of the battery under this example conditions.)

    P(AC) = 500W (inverter input)

    P(Load) = 3000W (load consumption)

    Grid Meter = -3500W (take from grid)

    The above condition lasts for 300s and then the AC port stops inputting. After this continues for 600s, the inverter returns to Backup mode.

    Mode 2: Electric Quantity Target Control Mode

    Model 2 Description:

    This mode controls the AC port of the inverter to input/output a certain amount of electric energy with a certain power. In this mode the PV runs at the highest possible power and the system can feed/take power to/from the grid.

    Exit logic: if the energy target value (0x0084 & 0x0085) is not updated within the set time (0x0088) after completing the commands, then this mode exits. When the energy target value is not reached, the mode runs until the next command is entered.

    Control Mode

    Register

    Variable

    Unit

    mode 2

    (electric quantity target control mode)

    0x007C

    ModbusPowerControl

    1

    0x007D

    TargetSetType

    1

    0x0084

    TargetEnergy

    1Wh

    0x0085

    0x0086

    Charge_Discharg_Power

    1W

    0x0087

    0x0088

    RemoteCtrlTimeOut

    1s

    • If a command is given to set the power “+x” W (x>0), it means that we want the inverter AC port to [input] active power “x” W. That is, at this point, the load is fully fed by the grid, and in addition to the load's consumption, the inverter buys “x” W of electrical power from the grid.

    Like mode 1, here in Mode 2, when AC port input power, it contains exactly the same three categorized discussion scenarios. Therefore, for details on these scenarios please refer to the “Model 1 Description”.

    • If a command is given to set the power “-x” W (x>0), it means that we want the inverter AC port to [output] active power “x” W.

    Like mode 1, here in Mode 2, when AC port output power, it also contains exactly the same three categorized discussion scenarios. Therefore, for details on these scenarios please refer to the “Model 1 Description”.

    Case study 2.1:

    • Pre-commission:

    X3-Hybrid G4 + 4*T30, Inverter work mode: Self-Use Mode, Battery SOC: 20%

    P(PV) = 1000W

    P(BAT) = 0

    P(AC) = -1000W (inverter output)

    P(Load) = 1000W (load consumption)

    Grid Meter = 0

    • User Requirement:

    Let the AC port of the inverter input 2000Wh into the system with a power of 1000W.

    • Write Command:

    Register

    Variable

    Unit

    Case Study 2.1

    (decimal)

    Write Value

    (hexadecimal)

    0x007C

    ModbusPowerControl

    1

    2

    0x0002

    0x007D

    TargetSetType

    1

    1

    0x0001

    0x0084

    TargetEnergy

    1Wh

    2000

    0x07D0

    0x0085

    0x0000

    0x0086

    Charge_Discharg_Power

    1W

    1000

    0x03E8

    0x0087

    0x0000

    0x0088

    RemoteCtrlTimeOut

    1s

    600

    0x0258

    • Situation under Remote Control Mode 2 (for example only, not a real situation):

    Electric Quantity Target Control Mode

    P(PV) = P(PV max) = 1000W

    P(BAT) = 1500W (battery charging) (It is the maximum charging power of the battery under this example conditions.)

    P(AC) = 500W (inverter input) (The request for the command was not achieved, but the system will not report an error.)

    P(Load) = 1000W (load consumption)

    Grid Meter = -1500W (take from grid)

    The Electric Quantity Target Control Mode will exit after 600 seconds after 2000Wh is input to the AC port of the inverter and the inverter will return to Self-Use mode.

    Case study 2.2:

    • Pre-commission:

    X3-Hybrid G4 + 2*T30, Remote Control Mode 2, Battery SOC: 31%

    Before entering this remote control mode 2, the inverter’s work mode is Backup mode.

    P(PV) = 2000W

    P(BAT) = 1000W (battery charging)

    P(AC) = -1000W (inverter output)

    P(Load) = 1000W (load consumption)

    Grid Meter = 0

    • User Requirement:

    Update the target value in Mode 2, and let the AC port of the inverter output 9000Wh of electric energy with a power of 3000W.

    • Write Command:

    Register

    Variable

    Unit

    Case Study 2.2

    (decimal)

    Write Value

    (hexadecimal)

    0x007C

    ModbusPowerControl

    1

    2

    0x0002

    0x007D

    TargetSetType

    1

    2

    0x0001

    0x0084

    TargetEnergy

    1Wh

    2000

    0x07D0

    0x0085

    0x0000

    0x0086

    Charge_Discharg_Power

    1W

    -3000

    0xF448

    0x0087

    0xFFFF

    0x0088

    RemoteCtrlTimeOut

    1s

    600

    0x0258

    • Situation under Remote Control Mode 2 (for example only, not a real situation):

    Electric Quantity Target Control Mode

    P(PV) = P(PV max) = 2000W

    P(BAT) = -1000W (battery discharging)

    P(AC) = -3000W (inverter output)

    P(Load) = 1000W (load consumption)

    Grid Meter = 2000W (feed into grid)

    After some time, the battery SOC will drop to the system default minimum SOC, 10%. At this time, the battery is no longer discharged, so the output of the system is only provided by the PV. If the current PV power can meet the requirements of the command, then the system outputs according to the requirements of the command; if the current PV power cannot meet the requirements of the command, then the system outputs according to the maximum power at the moment.

    The Electric Quantity Target Control Mode will exit after 600 seconds after the AC port of the inverter output 9000Wh and the inverter will return to Backup mode.

    Mode 3: SOC Target Control Mode

    Model 3 Description:

    This mode controls the AC port of the inverter to input/output with a certain power and takes the battery SOC as the target value. In this mode the PV runs at the highest possible power and the system can feed/take power to/from the grid.

    Exit logic: if the SOC target value (0x0083) is not updated within the set time (0x0088) after completing the commands, then this mode exits. When the SOC target value is not reached, the mode runs until the next command is entered.

    Note: This mode can only work when the current battery SOC has not reached the target SOC. For example, if the current battery SOC is 50% and the command requires a certain power input from the AC port and the target SOC is 40%, then the system will directly exit the SOC target control mode.

    Control Mode

    Register

    Variable

    Unit

    mode 3

    (SOC target control mode)

    0x007C

    ModbusPowerControl

    1

    0x0083

    TargetSoc

    1%

    0x0086

    Charge_Discharg_Power

    1W

    0x0087

    0x0088

    RemoteCtrlTimeOut

    1s

    Case study 3:

    • Pre-commission:

    X3-Hybrid G4 + 2*T30, Inverter work mode: Self-Use Mode, Battery SOC: 60%

    P(PV) = 3000W

    P(BAT) = 1000W (battery charging)

    P(AC) = -2000W (inverter output)

    P(Load) = 2000W (load consumption)

    Grid Meter = 0

    • User Requirement:

    Set the output power of the AC port of the inverter to 4000W and discharge the battery to 30% SOC.

    • Write Command:

    Register

    Variable

    Unit

    Case study 3 (decimal)

    Write Value

    (hexadecimal)

    0x007C

    ModbusPowerControl

    1

    3

    0x0003

    0x0083

    TargetSoc

    1%

    30

    0x001E

    0x0086

    Charge_Discharg_Power

    1W

    -4000

    0xF060

    0x0087

    0xFFFF

    0x0088

    RemoteCtrlTimeOut

    1s

    600

    0x0258

    • Situation under Remote Control Mode 3 (for example only, not a real situation):

    SOC Target Control Mode

    P(PV) = P(PV max) = 3000W

    P(BAT) = -1000W (battery discharging)

    P(AC) = -4000W (inverter output)

    P(Load) = 2000W (load consumption)

    Grid Meter = 2000W (feed into grid)

    If the above working conditions are constant, then the SOC target (down to 30% SOC) will be completed in about 1.8 hours.

    Mode 4: Push Power - Positive/Negative Mode

    Model 4 Description:

    This mode directly controls the battery charging/discharging power, the PV power is as high as possible and the system can feed/take power to/from the grid.

    The positive and negative values of the data in this model are defined as: positive means battery discharge, negative means battery charge.

    Control Mode

    Register

    Variable

    Unit

    mode 4

    (Push Power - Positive/Negative Mode)

    0x007C

    ModbusPowerControl

    1

    0x0089

    PushModePower

    (Positive means battery discharge; Negative means battery charge)

    1W

    0x008A

    Case study 4.1:

    • Pre-commission:

    X3-Hybrid G4 + 4*T58, Inverter work mode: Self-Use Mode, Battery SOC: 70%

    P(PV) = 2000W

    P(BAT) = 0

    P(AC) = -2000W (inverter output)

    P(Load) = 2000W (load consumption)

    Grid Meter = 0

    • User Requirement:

    Battery discharging power 1000W;

    PV runs at maximum power if possible;

    • Write Command:

    Register

    Variable

    Unit

    Case study 4.1 (decimal)

    Write Value

    (hexadecimal)

    0x007C

    ModbusPowerControl

    1

    4

    0x0004

    0x0089

    PushModePower

    1W

    +1000

    0x03E8

    0x008A

    0x0000

    • Situation under Remote Control Mode 4 (for example only, not a real situation):

    Push Power – Positive/Negative Mode

    P(PV) = P(PV max) = 2000W

    P(BAT) = -1000W (battery discharging)

    P(AC) = -3000W (inverter output)

    P(Load) = 2000W (load consumption)

    Grid Meter = 1000W (feed into grid)

    Case study 4.2:

    • Pre-commission:

    Inverter work mode: Self-Use Mode

    P(PV) = 2000W

    P(BAT) = 0

    P(AC) = -2000W (inverter output)

    P(Load) = 2000W (load consumption)

    Grid Meter = 0

    • User Requirement:

    Battery charging power 1000W;

    PV runs at maximum power if possible;

    • Write Command:

    Register

    Variable

    Unit

    Case study 4.2 (decimal)

    Write Value

    (hexadecimal)

    0x007C

    ModbusPowerControl

    1

    4

    0x0004

    0x0089

    PushModePower

    (negative means battery charge)

    1W

    -1000

    0XFC18

    0x008A

    0XFFFF

    • Situation under Remote Control Mode 4 (for example only, not a real situation):

    Push Power – Positive/Negative Mode

    P(PV) = P(PV max) = 2000W

    P(BAT) = 1000W (battery charging)

    P(AC) = -1000W (inverter output)

    P(Load) = 2000W (load consumption)

    Grid Meter = -1000W (take from grid)

    Mode 5: Push Power - Zero Mode

    Model 5 Description:

    The battery does not charge or discharge, the PV power is as high as possible, and the system can feed/take power to/from the grid. The batteries remain powered but do not work, and the hybrid inverter is working similar to an on-grid inverter (string inverter).

    Control Mode

    Register

    Variable

    Unit

    mode 5

    (Push Power – Zero Mode)

    0x007C

    ModbusPowerControl

    1

    Case study 5:

    • Pre-commission:

    Inverter work mode: Self-Use Mode

    P(PV) = 2000W

    P(BAT) = 1000W (battery charging)

    P(AC) = -1000W (inverter output)

    P(Load) = 1500W (load consumption)

    Grid Meter = -500W (take from grid)

    • User Requirement:

    The battery does not charge or discharge, the PV power is as high as possible, and the system is allowed to feed/take power into/from the grid.

    • Write Command:

    Register

    Variable

    Unit

    Case study 5 (decimal)

    Write Value

    (hexadecimal)

    0x007C

    ModbusPowerControl

    1

    5

    0x0005

    • Situation under Remote Control Mode 5 (for example only, not a real situation):

    Push Power - Zero Mode

    P(PV) = P(PV max) = 2000W

    P(BAT) = 0

    P(AC) = -2000W (inverter output)

    P(Load) = 1500W (load consumption)

    Grid Meter = 500W (feed into grid)

    Mode 6: Self-Consume - Charge/Discharge Mode

    Model 6 Description:

    The battery can be charged from PV only, no charge from grid. Battery discharge depending on the load and PV. If the PV input power cannot cover the consumption of the load, then the battery can be discharged; if the battery is fully charged, then the excess PV power can be fed to the grid. The priority of the PV input is: load > battery > grid. This is like Self-Use mode.

    Control Mode

    Register

    Variable

    Unit

    mode 6

    (Self-Consume-Charge/Discharge Mode)

    0x007C

    ModbusPowerControl

    1

    Case study 6:

    • Pre-commission:

    X3-Hybrid G4 + 4*T58, Inverter work mode: Self-Use Mode, Battery SOC: 40%.

    A forced charging period has been set, during which the inverter is allowed to charge from the grid.

    P(PV) = 1000W

    P(BAT) = 5000W (battery charging)

    P(AC) = 4000W (inverter input)

    P(Load) = 3000W (load consumption)

    Grid Meter = -7000W (take from grid)

    • User Requirement:

    It's just like the description of mode 6.

    • Write Command:

    Register

    Variable

    Unit

    Case study 6 (decimal)

    Write Value

    (hexadecimal)

    0x007C

    ModbusPowerControl

    1

    6

    0x0006

    • Situation under Remote Control Mode 6 (for example only, not a real situation):

    Self-Consume - Charge/Discharge Mode

    P(PV) = P(PV max) = 1000W

    P(BAT) = -2000W (battery discharging)

    P(AC) = -3000W (inverter output)

    P(Load) = 3000W (load consumption)

    Grid Meter = 0

    Mode 7: Self-Consume - Charge Only Mode

    Model 7 Description:

    The battery can be charged from PV only, no charge from grid. Battery discharge is not allowed. Import from grid if necessary, export to grid if battery full.

    Control Mode

    Register

    Variable

    Unit

    mode 7

    (Self-Consume-Charge Only Mode)

    0x007C

    ModbusPowerControl

    1

    Case study 7:

    • Pre-commission:

    Inverter work mode: Self-Use Mode

    A forced charging period has been set, during which the inverter is allowed to charge from the grid.

    P(PV) = 1000W

    P(BAT) = 5000W (battery charging)

    P(AC) = 4000W (inverter input)

    P(Load) = 3000W

    Grid Meter = -7000W (take from grid)

    • User Requirement:

    It's just like the description of mode 7.

    • Write Command:

    Register

    Variable

    Unit

    Case study 7 (decimal)

    Write Value

    (hexadecimal)

    0x007C

    ModbusPowerControl

    1

    7

    0x0007

    • Situation under Remote Control Mode 7 (for example only, not a real situation):

    Self-Consume - Charge Only Mode

    P(PV) = P(PV max) = 1000W

    P(BAT port) = 0

    P(AC) = -1000W (inverter output)

    P(Load) = 3000W

    Grid Meter = -2000W (take from grid)

    Mode 8: PV&BAT Individual Setting – Duration Mode

    Mode 8 Description:

    The battery can be charged from PV and grid simultaneously, and PV power and BAT power can be set independently. In addition, the photovoltaic power generation can be limited to zero, ensuring that the inverter can absorb power from the grid at its maximum capacity.

    Exit: This mode is exited via Time of Duration(0X00A6).

    Control Mode

    Register

    Variable

    Unit

    mode 8

    (PV&BAT Individual Setting –

    Duration Mode)

    0x00A0

    PowerControlMode

    1

    0x00A1

    TargetSetType

    1

    0x00A2

    PVPowerLimit(LSB)

    1W

    0x00A3

    PVPowerLimit(MSB)

    1W

    0x00A4

    PushModePower(LSB)

    1W

    0x00A5

    PushModePower(MSB)

    1W

    0x00A6

    Time of Duration

    1s

    0x00A7

    RemoteControlTimeOut

    1s

    Case Study 8:

    • Pre-commission:

    Work Mode = self-use

    Max Discharge current = 30.0

    Max charge current = 30.0

    No limit in Export Control / Power Limit / Main Breaker Limit

    A forced charging period has been set, during which the inverter is allowed to charge from the grid.

    • Scenario:

    P(PV) = 1000 W

    P(BAT) = 5000 W (battery charging)

    P(AC) = 4000 W (inverter take-in)

    P(Load)= 3000W

    Grid Meter = -7000W (absorb from grid)

    • User Requirement:

    PV Power can be restricted to 0 W.

    Maximal absorption of grid power during negative-tariff period.

    According to negative-tariff period, inverter can execute for a certain period of time. (For example, 30 minutes)

    • Write Command:

    Register

    Variable

    Unit

    Write Value

    (decimal)

    Write Value

    (hexadecimal)

    0x00A0

    PowerControlMode

    1

    8

    0x0008

    0x00A1

    TargetSetType

    1

    1

    0x0001

    0x00A2

    PVPowerLimit(LSB)

    1W

    0

    0x0000

    0x00A3

    PVPowerLimit(MSB)

    1W

    0

    0x0000

    0x00A4

    PushModePower(LSB)

    1W

    -5000

    0xEC78

    0x00A5

    PushModePower(MSB)

    1W

    0xFFFF

    0x00A6

    Time of Duration

    1s

    1800

    0x0708

    0x00A7

    RemoteControlTimeOut

    1s

    2000

    0x07D0

    **If TargetSetType == 2, this command will execute for 30min. (Based on the start time of the former command)

    • After command:

    P(PV) = 0 W

    P(BAT) = 5000 W (battery charging)

    P(AC) = 4000 W (inverter take-in)

    P(Load)= 3000W

    Grid Meter = -8000W (absorb from grid)

    You will take in more electric energy (Approximately 0.5kWh, if BAT power is higher than 1000W at any time) from Grid, and earn more during negative-tariff period.

    Mode 9: PV&BAT Individual Setting – Target SOC Mode

    Mode 9 Description:

    The battery can be charged from PV and grid simultaneously, and PV power and BAT power can be set independently. In addition, the photovoltaic power generation can be limited to zero, ensuring that the inverter can absorb power from the grid at its maximum capacity.

    Exit: This mode is exited via Target SOC.

    Control Mode

    Register

    Variable

    Unit

    mode 9

    (PV&BAT Individual Setting –

    Target SOC Mode)

    0x00A0

    PowerControlMode

    1

    0x00A1

    TargetSetType

    1

    0x00A2

    PVPowerLimit(LSB)

    1W

    0x00A3

    PVPowerLimit(MSB)

    1W

    0x00A4

    PushModePower(LSB)

    1W

    0x00A5

    PushModePower(MSB)

    1W

    0x00A6

    Target SOC

    1%

    0x00A7

    RemoteControlTimeOut

    1s

    Case Study 9:

    • Pre-commission:

    Work Mode = self-use

    Max Discharge current = 30.0

    Max charge current = 30.0

    No limit in Export Control / Power Limit / Main Breaker Limit

    A forced charging period has been set, during which the inverter is allowed to charge from the grid.

    • Scenario:

    P(PV) = 1000 W

    P(BAT) = 5000 W (battery charging)

    SOC(BAT) = 30% (T30*2)

    P(AC) = 4000 W (inverter take-in)

    P(Load)= 3000W

    Grid Meter = -7000W (absorb from grid)

    • User Requirement:

    PV Power can be restricted to 0 W.

    Maximal absorption of grid power during negative-tariff period.

    Set a certain Target SOC. (For example, 80%)

    • Write Command:

    Register

    Variable

    Unit

    Write Value

    (decimal)

    Write Value

    (hexadecimal)

    0x00A0

    PowerControlMode

    1

    8

    0x0008

    0x00A2

    PVPowerLimit(LSB)

    1W

    0

    0x0000

    0x00A3

    PVPowerLimit(MSB)

    1W

    0

    0x0000

    0x00A4

    PushModePower(LSB)

    1W

    -5000

    0xEC78

    0x00A5

    PushModePower(MSB)

    1W

    0xFFFF

    0x00A6

    Target SOC

    1%

    80

    0x0050

    0x00A7

    RemoteControlTimeOut

    1s

    3600

    0x0E10

    • After command:

    P(PV) = 0 W

    P(BAT) = 5000 W (battery charging)

    SOC(BAT) = 80% (T30*2)

    P(AC) = 5000 W (inverter take-in)

    P(Load)= 3000W

    Grid Meter = -8000W (absorb from grid)

    You will take in more electric energy (Approximately 0.6kWh, if BAT power is higher than 1000W at any time) from Grid, and earn more during negative-tariff period.

    Querying set parameters

    This section is used to verify that the currently running remote control mode is working as expected according to the set parameter values.

    The query of related set parameters and the reference of the target setting range in the first, second and third modes, are provided in the function code 0x04 (Read Input Register) register, address 0x0100~0x011E, as shown below.

    About Cookies

    We use cookies to enhance your browsing experience, serve personalized ads or content, and analyze our traffic. By clicking "Accept All", you consent to our use of cookies.
    Accept Reject