    Meter CT Self Check

    Background

    Meter and CT is the Measuring device installed at the GCP (Grid Connection Point) of the inverter system for detecting GCP data. For energy storage system, the functions such as Battery Charge and Discharge, Working Mode, Export Control and Three-phase Unbalanced,

    can only be achieved when the Measurement device is installed correctly.

    The Meter/CT Self-Check function can identify whether there has problems with the Meter and CT installation through the feedback of the power changes. After the installation is completed, you just need to use this function, then you can troubleshoot the problems on site.

    What problems can be troubleshooted with Meter/CT Self-Check Function?

    Some problems can be corrected automatically, and others need to be manually adjusted by the installer based on the error code displayed after the checking is completed.

    (1) For the following Installation problems, the inverter will adjust the correspondence with Measurement Device to Automatically Correct them:

    ① ‘CT’ direction is reversed

    ② ‘CT’ three phases correspondence is not correct

    Note: Meter’s three phases correspondence problem can also be Automatically Corrected.

    (2) These installation problems need to be Manually Corrected by the installer according to the error code prompt: (Error codes refer to Table 1)

    ① 'CT' has not been successfully clipped on the phase wire

    ② 'CT' is wrongly connected to the loads side

    ③ 'CT' is wrongly connected between the loads and the inverter

    ④ The CT is connected to the N wire

    ⑤ Two CTs are connected to the same phase.

    C:\Users\lenovo\AppData\Local\Microsoft\Windows\INetCache\Content.Word\C-两个CT一根线.png

    ⑥ The CT is connected to 2 wires

    ⑦ The direction of ‘Meter-CT’ is reversed

    Note: Meter’s direction reverse problem also need to be Manually Corrected according to the error code prompt.

    ⑧ ‘Meter-CT’ three phases correspondence is not correct

    Note: If there has communication problem with Meter and Meter-CT, the ‘Meter fault’ will be reported.

    How to Use the Meter and CT Self-Check Function?

    After the installation is completed, the installer can enable the ’Installation Check’ on the LCD screen or the SolaX Cloud, the inverter will detect whether the Meter and CT has been installed correctly. The inverter will automatically correct it or display the corresponding error code if there has problem.

    The Table 1 describes the meaning of error codes.

    Tab.1 The Error Codes and Corresponding Meaning

    Error Codes

    Meaning

    Fail 00

    Phase A has no CT clipped on it.

    Fail 01

    Phase A has 2 CTs clipped on it, or there is CT clipped on the N wire.

    Fail 02

    CT1 is clipped to Phase A and Phase B.

    Fail 03

    CT2 is clipped to Phase A and Phase B.

    Fail 04

    CT3 is clipped to Phase A and Phase B.

    Fail 05

    Phase B has no CT clipped on it.

    Fail 06

    Phase B has 2 CTs clipped on it, or there is CT clipped on the N wire.

    Fail 07

    CT1 is clipped to Phase A and Phase C.

    Fail 08

    CT2 is clipped to Phase A, CT1 is clipped on Phase B and Phase C.

    Fail 09

    CT3 is clipped to Phase A, CT1 is clipped on Phase B and Phase C

    Fail 10

    CT2 is clipped to Phase A and Phase C.

    Fail 11

    CT1 is clipped to Phase A, CT2 is clipped on Phase B and Phase C

    Fail 12

    CT3 is clipped to Phase A, CT2 is clipped on Phase B and Phase C

    Fail 13

    CT3 is clipped to Phase A and Phase C.

    Fail 14

    CT1 is clipped to Phase A, CT3 is clipped on Phase B and Phase C

    Fail 15

    CT2 is clipped to Phase A, CT3 is clipped on Phase B and Phase C

    Fail 16

    Phase C has no CT clipped on it.

    Fail 17

    Phase C has 2 CTs clipped on it, or there is CT clipped on the N wire.

    Fail 18

    No reactive power was detected on phase A after adjusting the CT sequence.

    Fail 19

    No reactive power was detected on phase B after adjusting the CT sequence.

    Fail 20

    No reactive power was detected on phase C after adjusting the CT sequence.

    Fail 21

    Meter phase A direction is reversed.

    Fail 22

    Meter phase B direction is reversed.

    Fail 23

    Meter phase C direction is reversed.

    Fail 24~31

    Reservation

    Fail 32

    Not connected to the grid

    Fail 33

    The inverter reports an error and cannot run (see Error for details)

    Fail 34

    The inverter can not start normally (detection timeout)

    Fail 35

    ARM and DSP have not established effective communication.

    Fail 36

    CT is not connected to L phase

    Note: The error message is only a reminder and does not necessarily correspond to the actual installation problem. If the problem is not found after the error is reported, please contact SolaX service.

    Setting Path

    Advanced->Meter/CT Setting->Meter/CT Check->Installation Check

    Error Display

    ① Solax Cloud:

    The ‘Alarm’ page on the SolaX Cloud will show the “CT/Meter Check Fault” if there was Meter and CT installation problems. The detailed error code is shown on the Installation Check page on the LCD screen.

    ② LCD Screen

    On the Installation Check page, the ‘CT Status’ shows the current checking status. There are 4 statuses: Disable / Checking / Success / Fail xx, as shown in the figure.

    (Disable: Installation Checking is not enabled; Checking: Checking in progress; Success: Checking passed; Failed xx: Meter and CT has installation problem required manual adjustment)

    https://wework.qpic.cn/wwpic/71324_vhDIHEwiTBKm5BA_1694482854/0 https://wework.qpic.cn/wwpic/626145_XaaoNZgnTTSOvBZ_1694482863/0

    The Meter/CT Self-Check function of X1-Hybrid/Fit G4

    The Meter/CT Self-Check function of X1-Hybrid/Fit G4 has 2 differences from three-phase system in the following ways:

    Ⅰ. X1-Hybrid/Fit G4 only check CT and does not check meter;

    Ⅱ. Since X1-Hybrid/Fit G4 is single-phase inverter, there is no phase sequence corresponding issue.

    Here are the installation problems check of the single-phase system.

    (1) Automatically Correct

    If ‘CT direction reversed’ is detected, the inverter will Automatically correct the CT direction.

    (2) These problems will report ‘miss CT fault’ and need to be Manually Corrected by the installer.

    ① CT has not been successfully clipped on the phase wire

    ② CT is wrongly connected to the N wire

    ③ CT is connected to two wires

    ④ CT is wrongly connected to the loads side

    ⑤ CT is wrongly connected between the loads and the inverter

    Configuration

    Compatible Inverter Model:

    X1-Hybrid/Fit G4

    X3-Hybrid/Fit G4

    X3-ULTRA

    X1-IES

    X3-IES

    X3-AELIO

    X3-HYB-G4 PRO

    Firmware Version:

    X1-Hybrid/Fit G4:

    ARM≥1.34 DSP≥1.35

    X3-Hybrid/Fit G4:

    ARM≥1.28 DSP≥1.30

    X3-ULTRA(latest version):

    ARM≥018.02 DSP≥017.05

    X1-IES (latest version):

    ARM≥009.12 DSP≥013.12

    X3-IES (latest version):

    ARM≥012.05 DSP≥016.04

    X3-AELIO(latest version):

    ARM≥004.04 DSP≥004.05

    X3-HYB-G4 PRO(latest version):

    ARM≥005.11 DSP≥005.12

     

    Note: Both Inverter Parallel System and AC Coupling (with third-party string inverters) System all support Meter/CT Self-Check function.