In some high-latitude or high-altitude areas, the temperature (during winter) is quite low. The battery charging and discharging performance will be impacted significantly by the low temperature. SolaX developed a function of “Battery Heating” to make your ESS able to work under extreme low temperature.
This function is disabled by default, so you need to enable this function if needed.
After you enable this function, you need to set heating periods
The cell temperature is among -30 ~ 0℃, it will be heated until 10℃. Then, heating will stop, once the cell temperature is below 0℃ again, the battery system will be heated again.
The heating system will take energy from PV in priority. If the PV power is not enough, it will take energy from battery or grid, which depends on the BAT actual SOC.
If BAT actual SOC>35%, it takes from Battery.
If BAT actual SOC<35%, it takes from Grid.
The battery will be heated only if the PV has surplus energy.
Note:
Setting path:
Main → Settings → Advance Setting → Battery Heating → Func Select
Enable it and set heating periods.
Hardware version:
X1-Hybrid/Fit G4 T-BAT-SYS-HV 3.0
X3-Hybrid/Fit G4 T-BAT-SYS-HV S2.5/S3.6
Inverter software version:
ARM≥1.19 DSP≥1.22
Battery software version:
3.05 for T30 master (MC0600)