Issue introduction
After the battery is installed, it cannot be turned on, and the button does not respond.
Confirmation of basic information
[Photo]SN numbers of inverter and batteries.
Guidance for installer
Step1: Restart the battery correctly to see if it’s back to normal.
For T58: According to the following rules, dial the DIP switch to the correct number of normal connection use based on the actual number of batteries, then move the circuit breaker switch to “ON” and press the power button to start the battery. Remember to short-circuit the last battery.
Figure1. DIP switch
For T30:Move the circuit breaker switch to “ON” and press the power button for three seconds. When you hear the ‘Click’, the batteries have started successfully.
Step2: Check the connection of power cables and every terminal of batteries. Ensure that the cables are connected correctly and that the terminals are not damaged.
Figure2. X plug of T58
Figure3. Y plug of T58
Figure4. Power terminal of T30
Step3: Use a multimeter to measure the voltage of slave batteries as follows.
Table 1 Measure the voltage of each battery
Measure the voltage of T58 |
Measure the voltage of T30 |
Insert the red pen to the BAT+, and the black pen to the BAT-. Normal single T58 battery has a rated voltage of 115.2V, the operating voltage range of 100-131V. |
Use the same method to measure the voltage of T30, insert the pen into the round hole to the right of the terminal. A normal T30 single battery has a rated voltage value of 102.4V and the operating voltage range of 90-116V. |
If the voltage is lower than normal value, please enable the force charge mode on inverter or use a T-BAT-Charger to charge the battery.
When using inverter:
Setting path: Setting path: Work mode→Work mode→Manual→Force charge
Figure5. Force charge mode on inverter
When using T-BAT-Charger:
The setting path: Setting →forced charging →password:860829→enable
Figure6. Force charge mode on T-BAT-Charger
If one battery is still in low voltage after being charged, remove it then connect other batteries and start the system to ensure system running properly.
For T30, if the voltage is normal, try to activate the battery through PV. When the system is on grid, disable the charge from grid.
Setting path: Setting→User settings→Self Use→Charge from grid→Disable
Figure6. Disable the charge from grid
Then wait for PV voltage to increase to startup voltage, if batteries could turn on normally, it indicates a faulty switch in the BMS, so replace the BMS.
Step4: Upgrade battery and inverter to the latest firmware version, then restart the batteries.
Information check list
If you have completed the above <Guidance for installer>, and the problem is still not solved, please collect the following troubleshooting information and send them to the R&D.
1.[Photo] Inverter and battery information including SN and registration number.
2. [Video] Progress of turning on the battery.
3. [Video] Power connection of batteries.
4. [Photo] Terminals of batteries.
5.[Photo]Voltage of batteries.
The voltage of T58 |
The voltage of T30 |